Product overviewThe round DRE pressure regulator maintains a set pressure in a room or in supply/exhaust air ducts and can also be used to shut off air ducts. It is suitable for polluted or chemically contaminated air. Static pressure in the duct or room is measured; the setpoint is compared with the measured value and the control damper is driven until the required setpoint is reached. Activation and control require external electrical power. The housing features push-in ends with lip seals suitable for air ducts to DIN EN 1506 / EN 13180.
Key benefits- Optimises system energy use by reducing required operating pressures
- Reduces control effort
- Can be combined with high-speed drives
- Optional additional volume flow measurement
- Available with dynamic (DRE) or static (DRE-s) measuring principle
ApplicationsUse, for example, in conjunction with induction devices. Suitable for maintaining constant pressure levels in rooms or ducts and for airtight shut-off functions.
Design / Options- Housing versions: galvanized steel, coated, stainless steel
- Push-in ends with lip seals for duct connection (DIN EN 1506 / EN 13180)
- Optional silencer: SDE
- Measuring principle: dynamic (standard for non-polluted air) or static (optional for polluted air)
- Optional additional volume flow measurement
- Electric external actuation; compatible with high-speed actuators
Technical data / Specifications- Differential pressure range: up to 1000 Pa
- Airtight shut-off: DIN EN 1751 Class 4 (DN 100 + 125: Class 3)
- Available sizes: Ø 100 - 400 mm
- Housing materials: galvanized steel, coated, stainless steel
- Optional silencer: SDE
- Measuring principles: dynamic (DRE) or static (DRE-s)
- Optional additional volume flow measurement
- Push-in ends with lip seals for air ducts to DIN EN 1506 / EN 13180