Product overviewThe round VRE volume flow regulators provide continuous and variable control of air volume flow; full shut-off is also possible. Depending on the configuration, units are suitable for polluted or non-polluted air. Actuation and control require external energy, available as electric or pneumatic drives. Push-in ends with insertion bead for lip seal allow connection to air ducts to DIN EN 1506 or EN 13180, or to flanges to DIN 24154 series 1 from nominal size DN 500.
Versions / Features- Steel – galvanized, coated, stainless steel
- PPS – for aggressive media, all components in the air flow made of plastic
- Attachment of various controller makes/components possible
- Can be combined with spring-return or high-speed drives
- Corrosion-resistant versions available
- Measuring principle: dynamic (VRE) or static (VRE-s)
Technical data- LpA: 35 dB(A)
- Volume flow ranges: entries shown on page include "19 - approx. 11" and "200 m³/h"
- Differential pressure range: up to 1000 Pa
- Casing leakage according to DIN EN 1751: Class A (standard), Class C optional
- Airtight shut-off according to DIN EN 1751: Class 4 (DN 100 and 125: Class 3)
- Sizes [mm]: Ø 100 - 600
- Actuation/control: external energy (electric or pneumatic)
- Connections: push-in ends with insertion bead for lip seal; suitable for ducts to DIN EN 1506 or EN 13180 and flanges to DIN 24154 series 1 from DN 500
Design / Options- Galvanized steel
- Coated
- Stainless steel
- PPS (plastic)
- Silencer SDE (optional)
- Measuring principle: dynamic (for non-polluted air) or static (for polluted air) (optional)
- Various housing versions available
Characteristics / technical specifications- LpA: 35 dB(A)
- Volume flow ranges and examples as shown above
- Differential pressure range up to 1000 Pa
- Casing leakage: DIN EN 1751 Class A standard, Class C optional
- Airtight shut-off: DIN EN 1751 Class 4 (DN 100 + 125: Class 3)
- Available sizes: Ø 100 - 600 mm
- Materials: galvanized steel, coated, stainless steel, PPS
- Optional silencer: SDE
- Measuring principles: dynamic (VRE) for non-polluted air, static (VRE-s) for polluted air
- Actuation/control: electric or pneumatic external drives
- Connections: push-in ends with insertion bead for lip seal; suitable for ducts and flanges per the standards listed